Advertisement

Protection functions
If the magnitude of the voltage level of any of the monitored voltage signal, defined
by the
Volt Blk value , the calculation of vector shift is disabled and the INT_BLKD output is
activated.
The function is blocked and LOWAMPL_BLKD is activated, if the measured frequency
deviates ±5% from the nominal value.
The magnitude of calculated vector shift for three phase-to-earth or phase-
to-phase voltages, USHIFT_A_AB, USHIFT_B_BC and USHIFT_C_CA or positive
sequence voltage U1SHIFT, which resulted in the activation of last OPERATE output,
are available in the Monitored data view.
The activation of BLOCK input deactivates the INT_BLKD output.
Figure 510: Vector shift during Loss of Mains
Pulse timer
Once the Pulse timer is activated, it activates the OPERATE output. The pulse length
of OPERATE is fixed to 100 ms.
The activation of the BLOCK input deactivates the OPERATE binary output and resets
the timer.
4.5.9.6
Application
Use of distributed generation ( DG) units is increasing due to liberalized markets
(deregulation) and the global trend to use more renewable sources of energy. They
generate power in the range of 10 kW...10 MW and most of them are interconnected
to the distribution network. They can supply power into the network as well as to
the local loads. It is not common to connect generators directly to the distribution
networks and thus the distributed generation can cause some challenges for the
protection of distribution networks. From the protection point of view, one of the
most challenging issue is islanding.
Islanding is defined as a condition in which a distributed generation unit continues
to supply power to a certain part of the distribution network when power from the
910
The recommended and the default value for
sequence".
Phase supervision setting, drops below Under Volt Blk value or exceeds Over
1MRS759142 F
Phase supervision is "Pos
REX640
Technical Manual