Monitored Data; Diagnostics - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
3.28.4

Monitored data

Monitored data is available in two locations.
• Monitoring > Communication > Ethernet > Activity > CH6LIV
• Monitoring > Communication > Ethernet > Link statuses > LNK6LIV
3.28.5

Diagnostics

Diagnostics data is available in Monitoring > Communication > Ethernet >
Diagnostics > X&.
Table 361: Parameters read from the SFP module connected in the X6/LD line differential channel
Parameter
Values (Range)
Temperature
–128.0...128.0
Voltage
0.000...6.550
Bias current
0.0...131.0
Tx power
0.000...6.550
Rx power
0.000...6.550
XCVR detected
FALSE / TRUE
Rx Power alarm
FALSE / TRUE
Tx Power alarm
FALSE / TRUE
Voltage alarm
FALSE / TRUE
Temperature alarm
FALSE / TRUE
Part name
SFP not inserted
SFP not supported
2RCA045621 (MM 2
km)
2RCA045622 (SM 20
km)
2RCA045623 (SM 50
km)
REX640
Technical Manual
Unit
Step
Default
C
0
V
0
mA
0
MW
0
mW
0
FALSE
FALSE
FALSE
FALSE
FALSE
SFP not inserted
Basic functions
Description
Measured SFP transceiver tem-
perature
Measured SFP transceiver volt-
age
Measured SFP transceiver bias
current
Measured SFP transceiver's
transmitter power
Measured SFP transceiver's re-
ceiver power
SFP Transceiver detection state
SFP Receiver power alarm
SFP Transmitter power alarm
SFP transceiver voltage alarm
SFP temperature alarm
Name, type and operational dis-
tance for the SFP module
325

Advertisement

Table of Contents
loading

Table of Contents