ABB RELION REX640 Technical Manual page 977

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
(2·Z
Figure 550: Tripping characteristic in case the zone characteristic is "Mho (circular)"
and Pol quantity zone is "Cross pol"
In case of positive-sequence polarization "Pos. seq. volt.", the polarization voltage
is the positive-sequence voltage. The voltage phase angle is rotated to match
the original fault loop voltage. The positive-sequence polarization expands the
tripping characteristic according to the prevailing system conditions. In case of
short circuit faults, the circle expands as a function of the source impedance
magnitude Z
source impedance and earthing impedance magnitudes: (Z
Phase-to-Earth
(Z
Figure 551: Tripping characteristic in case the zone characteristic is "Mho (circular)"
and Pol quantity zone is "Pos. seq. volt."
One alternative for polarization is also "Self pol" despite the drawbacks when using
it as a polarization method. The mho circle does not expand when using this
polarization method.
In case of cross and positive-sequence polarization, the expansion of the mho circle
is a positive feature as the fault resistance coverage is increased. The reach of the
zone is not affected by the expansion. The greatest expansion is obtained with
cross-polarization.
REX640
Technical Manual
Phase-to-Earth
X
+ Z
)/3 + Z
1source
0source
E
/2. In case of an earth fault, the circle expands as a function of
1source
X
(2·Z
+ Z
)/3 + Z
1source
0source
E
(2·Z
+ Z
)/3
1Line
0Line
R
Phase-to-phase/three-phase
+ Z
)/3
1Line
0Line
R
Protection functions
Phase-to-phase
X
Z
1Line
R
Z
1source
+ Z
1source
0source
X
Z
1Line
R
Z
/2
1source
)/3 + Z
.
E
977