Protection functions
Parameter
Values (Range)
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Table 738: NSPTOC Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Table 739: NSPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 740: NSPTOC Non group settings (Advanced)
Parameter
Values (Range)
Minimum operate
20...60000
time
Reset delay time
0...60000
824
Unit
Step
Unit
Step
Unit
Step
0.0001
0.0001
0.01
0.01
0.1
Unit
Step
ms
1
ms
1
1MRS759142 F
Default
Description
Default
Description
1=Immediate
Selection of reset
curve type
Default
Description
1=on
Operation Off / On
28.2000
Parameter A for
customer program-
mable curve
0.1217
Parameter B for
customer program-
mable curve
2.00
Parameter C for
customer program-
mable curve
29.10
Parameter D for
customer program-
mable curve
1.0
Parameter E for
customer program-
mable curve
Default
Description
20
Minimum operate
time for IDMT
curves
20
Reset delay time
Technical Manual
REX640

Advertisement

Table of Contents
loading