REX640 overview
2.4.1
Bay overview area
Bay overview area consists either of a static picture or a dynamic SLD. They
are configured with Graphical Display Editor in PCM600. One relay can have two
overview pages.
Static picture may be, for example, a drawing or a photo of switchgear lineup.
Maximum size of the picture is 186 × 320 px.
SLD does not support control operations. The following features are available.
• Static symbols such as connections, measurement devices, transformers and
reactors
• Dynamic status for switching devices, but no control operations
• Dynamic and static text objects
-
-
-
-
-
• Custom symbols
• Busbar coloring
2.4.2

Physical and virtual Home buttons

On the SHMI navigation page, the virtual Home button shows the status of each
relay as it would be shown with the physical Home button on a normal LHMI panel.
In normal situations, the virtual Home button shows a steady green light. All other
situations in which the relay requires operator's attention are indicated with a
flashing light, a red light or a combination of these.
SHMI's physical Home button has two operation modes.
• On the SHMI navigation page, the Home button indicates the combined status of
all connected relays. If multiple relays have different statuses, the Home button
shows the indication with the highest priority.
• On the HMI view, the Home button indicates the status of the respective relay as
described in
2.4.3

Navigation

Navigation page is the default view for the SHMI. The navigation page shows bay
overviews areas which are lined up to represent the actual panel installations. The
navigation page can be scrolled by swiping the screen horizontally or by pressing
the physical Home button to move the page from left to right one bay overview at a
time.
Bay overview area is the configured view for one relay. It may show static or dynamic
information but all control operations are disabled. The whole bay overview area
works as a navigation point to the relay's HMI view. Tapping this area opens the HMI
view of the respective relay.
Panel lineup overview shows the position of the navigation page by highlighting the
visible bay overviews. It also shows the status of all connected relays and helps in
52
Boolean state text
Integer state text
Label (translation not supported)
Numeric value
String value