Binary Input Signals; Analog Input Signals - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

Section 16
Monitoring
PostRetrig = Off
The function is insensitive for new trig signals during post fault time.
PostRetrig = On
The function completes current report and starts a new complete report that is, the latter will
include:
new pre-fault- and fault-time (which will overlap previous report)
events and indications might be saved in the previous report too, due to overlap
new fault locator and trip value calculations if installed, in operation and started
Operation in test mode
If the IED is in test mode and
any recordings and no LED information is displayed.
If the IED is in test mode and
mode and the status is indicated in the saved recording.
16.6.3.2

Binary input signals

Up to 352 binary signals can be selected among internal logical and binary input signals. The
configuration tool is used to configure the signals.
For each of the 352signals, it is also possible to select if the signal is to be used as a trigger for
the start of the Disturbance report and if the trigger should be activated on positive (1) or
negative (0) slope.
OperationN : Disturbance report may trig for binary input N ( On ) or not ( Off ).
TrigLevelN : Trig on positive ( Trig on 1 ) or negative ( Trig on 0 ) slope for binary input N.
Func103N : Function type number (0-255) for binary input N according to IEC-60870-5-103, that
is, 128: Distance protection, 160: overcurrent protection, 176: transformer differential
protection and 192: line differential protection.
Info103N : Information number (0-255) for binary input N according to IEC-60870-5-103, that is,
69-71: Trip L1-L3, 78-83: Zone 1-6.
See also description in the chapter IEC 60870-5-103.
16.6.3.3

Analog input signals

Up to 40 analog signals can be selected among internal analog and analog input signals.
PCM600 is used to configure the signals.
The analog trigger of Disturbance report is not affected if analog input M is to be included in
the disturbance recording or not (
OperationM = Off , no waveform (samples) will be recorded and reported in graph. However,
If
Trip value, pre-fault and fault value will be recorded and reported. The input channel can still be
used to trig the disturbance recorder.
394
OpModeTest = Off . Disturbance report function does not save
OpModeTest = On . Disturbance report function works in normal
For retrieving remote data from LDCM module, the Disturbance report function
should not be connected to a 3 ms SMAI function block if this is the only
intended use for the remote data.
OperationM = On / Off ).
1MRK 511 358-UEN A
M12179-492 v4
M12179-90 v7
M12179-92 v4
Application manual