ABB RELION REX640 Technical Manual page 729

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
High operate value
Low operate value
Figure 413: Operating characteristics of the protection. LS stands for the biased low
stage and HS for the instantaneous high stage
The OPERATE output is always activated with the OPR_HS output. The internal
blocking signals of the differential function do not prevent the trip signal of the
instantaneous differential current stage from being activated. When required, the
operating outputs of Instantaneous high stage can be blocked by the external
control signals BLK_OPR_HS or BLOCK.
Fault in protected area
(from Differential calculation)
(from Differential calculation)
Figure 414: Operation logic of Instantaneous high stage
External blocking functionality
TR3PTDF has three inputs for blocking.
REX640
Technical Manual
Id/Ir
OPERATE
AREA (LS)
Slope
section 2
End section 1
I_D
BLOCK
BLK_OPR_HS
High operate value
OPERATE
AREA (HS)
Slope
section 3
NON-OPERATE
AREA (LS & HS)
End section 2
Protection functions
NON-OPERATE
AREA (LS)
Ib/Ir
OPERATE
OPR_HS