Load Profile Ldprlrc (Ansi Loadprof); Identification; Function Block; Functionality - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
3.24

Load profile LDPRLRC (ANSI LOADPROF)

3.24.1

Identification

Function description
Load profile recorder
3.24.2

Function block

Figure 188: Function block
3.24.3

Functionality

The protection relay is provided with a load profile recorder. The load profile feature
stores the historical load data captured at a periodical time interval (demand
interval). Up to 12 load quantities can be selected for recording and storing in a
nonvolatile memory. The value range for the recorded load quantities is about eight
times the nominal value, and values higher than that saturate. The recording time
depends on a settable demand interval parameter and the amount of quantities
selected. The record output is in the COMTRADE format.
3.24.3.1
Quantities
Table 341: Signals supported by the load profile recorder
Function
CMMXU
Table continues on the next page
REX640
Technical Manual
IEC 61850
identification
LDPRLRC
Signal
I_DMD_A
I_DMD_B
I_DMD_C
Basic functions
IEC 60617
ANSI/IEEE C37.2
identification
device number
LOADPROF
LOADPROF
Description
Demand value of IL1 current
Demand value of IL2 current
Demand value of IL3 current
311