1MRS759142 F
4.2.6.7
Signals
HAEFPTOC Input signals
Table 585: HAEFPTOC Input signals
Name
IRES
BLOCK
I_REF_RES
HAEFPTOC Output signals
Table 586: HAEFPTOC Output signals
Name
OPERATE
START
4.2.6.8
HAEFPTOC Settings
Table 587: HAEFPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
0.05...5.00
Time multiplier
0.025...15.000
Operate delay time
100...300000
Operating curve
1=ANSI Ext. inv.
type
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
REX640
Technical Manual
Type
SIGNAL
BOOLEAN
FLOAT32
Type
BOOLEAN
BOOLEAN
Unit
Step
xIn
0.01
0.005
ms
10
Protection functions
Default
Description
-
Residual current
0=False
Block signal for acti-
vating the blocking
mode
0.0
Reference current
Description
Operate
Start
Default
0.10
1.000
600
15=IEC Def. Time
Description
Start value
Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time
Selection of time
delay curve type