ABB RELION REX640 Technical Manual page 991

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Parameter
Values (Range)
R0 zone 4
0.00...3000.00
X0 zone 4
0.00...3000.00
Factor K0 zone 4
0.00...5.00
Factor K0 angle
-179...180
Zn4
Min Ris Gnd Rch
0.00...500.00
Zn4
Max Ris Gnd Rch
0.00...500.00
Zn4
Gnd operate Dl Zn4 20...60000
Directional mode
1=Non-directional
Zn5
2=Forward
3=Reverse
Op Mod PP loops
0=False
Zn5
1=True
PP Op delay Mod
0=False
Zn5
1=True
R1 zone 5
0.00...3000.00
X1 zone 5
0.00...3000.00
X1 reverse zone 5
0.00...3000.00
Z1 zone 5
0.01...3000.00
Z1 angle zone 5
15.0...90.0
Z1 reverse zone 5
0.00...3000.00
Min Ris PP Rch Zn5
0.00...100.00
Max Ris PP Rch Zn5 0.00...100.00
PP operate delay
20...60000
Zn5
Op Mod Gnd loops
0=False
Zn5
1=True
Gnd Op Dl mode
0=False
Zn5
1=True
Load Comp zone 5
0=False
1=True
Table continues on the next page
REX640
Technical Manual
Unit
Step
ohm
0.01
ohm
0.01
0.01
deg
1
ohm
0.01
ohm
0.01
ms
1
ohm
0.01
ohm
0.01
ohm
0.01
ohm
0.01
deg
0.1
ohm
0.01
ohm
0.01
ohm
0.01
ms
1
Protection functions
Default
Description
160.00
Zero sequence re-
sistive reach, zone
4
160.00
Zero sequence re-
active reach, zone 4
1.00
Residual compen-
sation factor mag-
nitude, zone 4
0
Residual compen-
sation factor angle,
zone 4
100.00
Minimum resistive
reach of PE-loops,
zone 4
100.00
Maximum resistive
reach of PE-loops,
zone 4
20
Time delay to op-
erate of PE-loops,
zone 4
2=Forward
Directional mode,
zone 5
0=False
Enable PP/3P-loop
measurement, zone
5
1=True
Enable operate tim-
er for PP/3P-loops,
zone 5
40.00
ositive sequence
resistive reach,
zone 5
40.00
Positive sequence
reactive reach, zone
5
40.00
Pos. seq. reactive
reach in rev. dir.,
non-dir. zone 5
56.57
Positive sequence
reach, zone 5
45.0
Positive sequence
line angle, zone 5
56.57
Positive sequence
reach in rev. dir.,
non-dir. zone 5
30.00
Minimum resistive
reach of PP/3P-
loops, zone 5
30.00
Maximum resistive
reach of PP/3P-
loops, zone 5
20
Time delay to oper-
ate of PP/3P-loops,
zone 5
0=False
Enable PE-loop
measurement, zone
5
1=True
Enable operate tim-
er for PE-loops,
zone 5
1=True
Enable load com-
pensation for PE-
loops, zone 5
991

Advertisement