Setting the forced stop
To use the "Forced stop function", set the following data using a program.
"[Pr.82] Forced stop valid/invalid selection" is validated at the rising edge (OFF ON) of the PLC READY signal [Y0] and
"[Cd.158] Forced stop input" checks in the operation cycle.
"[Cd.158] Forced stop input" is validated only when "[Pr.82] Forced stop valid/invalid selection" is set to "2: Valid (Buffer
memory)".
Setting item
[Pr.82]
Forced stop valid/invalid
selection
[Cd.158]
Forced stop input
*1 A value other than "1" is regarded as "0".
Refer to the following for the setting details.
Page 411 Basic Setting
How to check the forced stop
To use the states (ON/OFF) of forced stop input, set the parameters shown in the following table.
Monitor item
[Md.50]
Refer to the following for information on the storage details.
Page 479 Monitor Data
Precautions during control
• After the "Forced stop input" is released, the servo ON/OFF is valid for the status of all axis servo ON [Y1].
• If the setting value of "[Pr.82] Forced stop valid/invalid selection" is outside the range, the error "Forced stop valid/invalid
setting error" (error code: 1DC1H) occurs.
• "[Md.50] Forced stop input" is stored "1" by setting "[Pr.82] Forced stop valid/invalid selection" to "1: invalid".
• When the "Forced stop input" is turned ON during operation, the error "Servo READY signal OFF during operation" (error
code: 1A02H) does not occur.
• The status of the signal that is not selected in "[Pr.82] Forced stop valid/invalid selection" is ignored.
• Errors cannot be cleared by "[Cd.5] Axis error reset" during forced stop. Clear errors after forced stop is released.
• If "[Cd.158] Forced stop input" is set to "0000H: Forced stop ON (Forced stop)" during the operation with "[Pr.140] Driver
command discard detection setting" set to "1: Detection enabled", an error "Driver command discard detection" (error code:
1BE6H) may occur before turning the servo OFF.
Downloaded from
ManualsNet.com
Setting
value
Forced stop input
search engine
Setting details
Set the forced stop function.
1: Invalid
Forced stop is not used
2: Valid (Buffer memory)
Forced stop from the buffer
memory is used
Set the forced stop information to the buffer memory.
0: Forced stop ON (Forced
Forced stop
*1
stop)
1: Forced stop OFF (Forced
Forced stop release
stop release)
Monitor
Storage details
value
Stores the states (ON/OFF) of forced stop input.
0: Forced stop input ON (Forced stop)
1: Forced stop input OFF (Forced stop release)
Buffer memory address
Axis 1 to axis 16
35
5945
Buffer memory
address
Axis 1 to axis 16
4231