4.3

Relation between various controls and block start data

The "block start data" must be set to carry out "high-level positioning control".
The setting requirements and details of each "block start data" item to be set differ according to the "[Da.13] Special start
instruction" setting.
The following shows the "block start data" setting items corresponding to various control methods.
Also refer to the following for details on "condition data" with which control execution is judged.
Page 150 Setting the Condition Data
(The "block start data" settings in this chapter are assumed to be carried out using the engineering tool.)
: One of the two setting items must be set
: Set as required (Set to "" when not used)
: Setting not possible
: Setting not required (Set the initial value or a value within the setting range.)
Block start data setting
items
[Da.11]
Shape
[Da.12]
Start data No.
[Da.13]
Special start
instruction
[Da.14]
Parameter
*1 The "NEXT Start" instruction is used in combination with "repeated start (FOR Loop)" and "repeated start (FOR Condition)". Control
using only the "NEXT Start" will not be carried out.
It is recommended that the "block start data" be set whenever possible with the engineering tool. Execution by
a program uses many programs and devices. The execution becomes complicated, and the scan time will
increase.
Downloaded from
ManualsNet.com

Setting the Block Start Data

Block start
Condition
(Normal
Start
Start)
0: End
1: Continue
1 to 600
0
1
Condition data No.
search engine
Wait Start
Simultaneous
Repeated
Start
start (FOR
Loop)
2
3
4
Number of
repetitions
4 HIGH-LEVEL POSITIONING CONTROL
Repeated
NEXT Start
start (FOR
Condition)
5
6
Condition data
No.
4.3 Setting the Block Start Data
4
*1
141