Honeywell EK280 Applications Manual page 28

Volume converter
Hide thumbs Also See for EK280:
Table of Contents

Advertisement

EK280
a)
Start the "Auto-Encoder" function using the EK280 keypad as follows:
Open the calibration lock as described in the EK280 Operating Instructions.
Move the cursor to the "Serv." tab and via the path below to the value "Md.I1":
Serv.
Inputs
Press the ENTER key. ⇒ The set value flashes.
Repeatedly press one of the  or  arrow keys until the value "Auto-Encoder" flashes.
Press the ENTER key to confirm the value setting. Input can be canceled using the ESC key.
Wait until the "Auto-Encoder" display is updated with a new value. This can take up to a minute as
the EK280 activates and test all known encoder protocols consecutively.
On successful detection the EK280 displays the label "Vo" on the meter reading of the gas meter:
Serv.
Inputs
Close the EK280 calibration lock.
b)
Archiving of original counter value of the gas counter "Vo":
So that "Vo" (meter reading of the gas meter) is stored in the measurement period archive, daily archive and
monthly archive 1 instead of "VmG" (total operating volume), then use the parameterization program enSuite
to send the following parameter file to the EK280 ( chapter
i
After loading the WPP file, the measurement period archive, the daily archive and monthly
archives 1 and 2 are deleted!
EK280 - Archive1,3,7 Vo in Archive (ATTENTION Archives will be deleted!) (*)
c)
Archiving the operating volume, total ("VmG") (factory preset):
So that "VmG" (total operating volume) is stored in the measurement period archive, daily archive and
monthly archive 1 again (default setting) instead of "Vo" (meter reading of the gas meter), then use the
parameterization program enSuite to send the following parameter file to the EK280 ( chapter
parameter
file, p. 21):
i
After adding the WPP file, the measurement period archive, the daily archive and monthly
archives 1 and 2 are deleted!
EK280 - Archive1,3,7 VbG in Archive (ATTENTION Archives will be deleted!) (*)
The star * designates the file version, e.g., "a"
1
Application Manual
Input 1
Md.I1
input 1
Vo.
3.6 Send parameter
file, p.21):
26
1
3.6 Send
1