Honeywell EK280 Applications Manual page 135

Volume converter
Hide thumbs Also See for EK280:
Table of Contents

Advertisement

EK280
For parameterization of the COMFTP modem you need a commercially available DSUB9-RS232
parameterizing cable (1:1 through-contacted, no null-modem cable!) for the connection of your
PCs/laptops with the modem parameterizing interface (located on the modem adapter board of
the FE260, or a functioning GSM/CSD connection and the parameterizing program
WinPADS200-EK version V2.99 or later which you may download free of charge from
www.elster-instromet.com.
a) Closing the time windows
In order that the parameterization works correctly the time windows 5 and 6 must be closed. To do this:
Connect a PC with enSuite installed to the EK280 optical interface using the connection cable.
Start enSuite and set up the communication link to the EK280 using the optical interface.
( chapter
3.1 Setting up the communication link to the EK280 via optical
To do this select "Navigation" on the left-hand side and then
the navigation window.
In the top of the device window open the path "Parameters" > "Interfaces" by clicking on the relevant
plus signs, and then select
In call windows 5 and 6 set start and end to the same value for each one and then select the
"Transfer changes to device" icon at the top of the enSuite window.
Then wait a minute, for any communications activity in progress on the EK280 to be safely stopped.
b) Send parameter file
Depending on the modem type installed in the FE260, transmit one of the following parameter files to
the EK280 ( chapter
- Modem type "Integra M2106":
EK280_xvx. - FE260 & int. M2106+ (FW657e) - ComFTP (only V1.25) (*)
- Modem type "ECM-GW120":
EK280_xvx. - FE260 & int. ECM-GW-120 - ComFTP (*) 30
Also transmit the following further parameter file to the EK280.
EK2.. - Activate standard output data record for process data (*) 30
Set up the communication link via the optical interface between enSuite and the EK280 again.
7.4.7.8 ComFTP application parameterization in the FE260 modem
i
For parameterization of the COMFTP you need a commercially available cable for the serial data
transmission between your PC / laptop and the modem in the FE260, as well as the program
WinPADS200-EK version V2.99 or later which you may download free of charge from
www.elster-instromet.com. enSuite versions from V3.4 and higher cater for the editing of settings
in the ComFTP modem.
30
The "x" stands for the version of software on the device, e.g. "2v2".
The star * stands for a small letter which indicates the version of the file, e.g. "a".
Application Manual
"Call time
windows".
3.6 Send parameter
file, p. 21):
interface, p. 19)
"Parameterize
online" at the bottom of
30
133

Advertisement

Table of Contents
loading