EK280
Display
Designation
IPAdr
OwnIpAddress
Port
OwnTcpIpPort
DNS12
Dynamic Name Server 1
DNS22
Dynamic Name Server 2
i
Evidently, the correct APN data must be parameterized in order to establish a TCP connection.
The values entered above serve as dummy data, which must be overwritten with the correct
data.
Telephone book parameters
Display
Designation
Name
Telephonbook_Name
Serv.
Telephonbook_Sever
Port
Telephonbook_ServerPort
Login
Telephonbook_ServerUserNam
e
Passw
Telephonbook_ServerPassword
i
Dummy telephone book data is entered in the above table. Such data must naturally be
overwritten with the correct parameters to enable communication to take place.
The same Modbus master task list is parameterized for operations via an internal modem as for operations
via the terminal device ( chapter 8.2.6).
The parameterized trigger event must take place for communication to start. For testing communication, the
device on link 7 with parameter 7:D71 can be set with the brief description "TestC" to 1. The connection is
then started as a test. Otherwise there will be a wait until the parameterized trigger event takes place.
"x" = Instance of the telephone book (value range from 1-10)
50
Application Manual
Address
Value
3:783
3:784
40000
3:794
10.1.2.201
3:795
10.1.2.202
Table 15: Access-Point-Parameter
Address
"x"
50
x:D20
MdBusMast
er TCP_x
x:D27
10.1.13.251
x:D28
37357
x:D29
unknown
x:D2A
unknown
Table 16: Telephone book parameters
Content
Own IP address, this value is not
parameterized
Own port, via which a distant
client can create a TCP/IP
connection. This port must also be
known to the retrieving (client)
system!
Optional indication
Optional indication
Value
Content
IP address of the server to be
dialed
User name (with necessary
authentication on the server)
Password (with necessary
authentication on the server)