Honeywell EK280 Applications Manual page 216

Volume converter
Hide thumbs Also See for EK280:
Table of Contents

Advertisement

EK280
Message Status Name
b) Warnings
3
StSy
3
St.4
4
St.1
4
St.2
4
St.3
4
St.4
5
St.1
5
St.2
6
St.1
6
St.2
6
St.4
6
St.6
Application Manual
Description, Procedure
Dat.restaur.
E The batteries of the EK280 are intermittently dropping out. As a
result of this, the time has not changed and no measurement and
volume conversion have happened. However, all data is available.
This message appears when the battery is changed and the old
batteries are removed before the new ones are connected.
( Operating Instructions [1]).
Proceed with the help of the parameterization software enSuite:
Delete the status register
Vm warning
If a HF-NF switch is configured, then this message is enabled in
the event of a fault at the HF input, e.g. loss of external power
supply.
Outp.1 Error
There should be more pulses being emitted from the specified
output than are permitted under its configured settings.
Outp.2 Error
In order to eliminate the cause of the problem, you can use the
Outp.3 Error
parameterization software enSuite to either:
Outp.4 Error
In both cases, the change must be aligned with the connected
device.
I1-Warning
The encoder could not be read at the end of the measurement
period. The flow recording at this point is invalid.
I2 Pulse cmp
In the pulse comparison, e.g. between input 1 and input 2, the
deviation was too high ( chapter 4.4, p. 27).
W Warn Lim.
The displayed value is outside the set warning limit values.
The warning limits can be adjusted using the parameterization
software enSuite.
Vb Warn Lim. The monitored standard volume consumption value (default:
hourly consumption) is outside the set warning thresholds.
The monitored values and the warning limits can be adjusted
using the parameterization program enSuite.
Qm Warn
The actual flow rate (gas flow rate) is outside the set warning limit
Lim.
values.
The warning limits can be adjusted using the parameterization
program enSuite.
T Warn Lim.
The measured gas temperature is outside the set warning limit
values.
The warning limits can be adjusted using the parameterization
program enSuite.
Set the time of the EK280.
reduce the cp value of the output, or
increase the output frequency.