EK280
GSM operating mode
(p. 118).
Here the GPRS resp. UMTS modem in the EK280 functions as a TCP-Server and may be addressed by a
TCP client that is listed in its retrieval software through a static IP address. To allocate a static IP to the
modem during the setup of the GPRS resp. UMTS session, they must (together with their network provider)
maintain a virtual private network (VPN) which must be enabled on the SIM used in the modem.
Prerequisites for process described below:
The FE260 is connected and configured as described in  chapter 7.4.1.
The modem installed in the FE260 is suitable for TCPserv operation and is supported by the
software version installed in the connected EK280 (refer to table on  chapter
The SIM card is inserted and unlocked as described in  chapter 7.4.3.
The SIM card may be unlocked by entering the correct PIN in accordance with  chapter 7.4.4.
7.4.6.1 EK280 Parametrization
i
A modem parameterized for TCPserv operation can still be called via the CSD
(GSM operation  Chapter 7.4.5). However, a CSD connection cannot consist of a TCP
connection at the same time: only one after the other!
i
For parameterization of the EK280 you need a connection cable for the optical interface as well
as the enSuite program. enSuite can be downloaded free of charge from the Honeywell website
in the "Software Downloads" section:
www.elster-instromet.com/en/software-downloads
a) Closing the time windows
In order that the parameterization works correctly the time windows 5 and 6 must be closed. To do this:
Connect a PC with enSuite installed to the EK280 optical interface using the connection cable.
Start enSuite and set up the communication link to the EK280.
( chapter
3.1 Setting up the communication link to the EK280 via optical
Select "Navigation" on the left-hand side and then
navigation window.
In the top of the device window open the path "Parameters" > "Interfaces" by clicking on the relevant
plus signs, and then select
In call windows 5 and 6 set start and end to the same value for each one and then select the
"Transfer changes to device" icon at the top of the enSuite window.
Then wait a minute, for any communications activity in progress on the EK280 to be safely stopped.
b) Sending parameter file
Depending on the modem module fitted to the FE260 and the loaded modem application (this can be
determined from the modem sticker,  chapter
modems in the
FE260, p. 124) send one of the following parameter files to K280 ( chapter
Send parameter
CSD=Circuit Switched Data, circuit-switched data service in the case of mobile telephony.
26
Application Manual
"Call time
windows".
file, p. 21):
"Parameterize
online" at the bottom of the
7.4.6.2 Parameterization of the GPRS/TCPserv
121
7.4.2).
connection
26
interface, p. 19)
3.6

Advertisement