3.6 (Optional) Installing a 600 mm Wide Air Conditioner
Enclosure Frame
Context
To increase the equipment depth to 1200 mm, install enclosure frames whose BOM number is
21242025 on the front doors of air conditioners.
Figure 3-36 Installed enclosure frame
(1) Enclosure frame
Procedure
Step 1 Open the front door, and remove the LCD power cable and the front door ground cable. Then
lift and remove the front door.
Step 2 Use four M5 tapping screws to secure one upper sealing plate to the enclosure frame.
There are two upper sealing plates, and the one used in this step has no gap. Figure 3-37
shows the upper sealing plates of an enclosure frame.
Issue 04 (2017-06-30)