Drainpipe - Huawei FusionModule2000 Installation Manual

Smart modular data center, 2000 mm high cabinets, single-row aisle containment, 380 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)

3.1.3.5 Drainpipe

A drainpipe should be able to withstand a temperature greater than 85° C. Otherwise, pipe
deformation may occur (for equipment configured with a humidifier).
A drainpipe can be connected in two ways:
Determine a pipe connection method based on site pipe materials.
Figure 3-15 Connecting a drainpipe
(1) Rigid pipe: 1/2-inch BSPT, external thread, made of PP-R,
C-PVC, or other materials
(3) Hose: inner diameter of 14 mm, made of EPDM or other
materials
(5) Rigid pipe conversion adapter: 5/8-inch outer diameter,
adapting for 1/2-inch BSPP internal thread connection
Issue 04 (2017-06-30)
Components inside the dashed-line boxes are ports on the equipment. Component 3 is mandatory. Other
components are subject to engineering procurement.
Top pipe routing: For the connection method of the water pump drainpipe, see method A
in Figure 3-15.
Bottom pipe routing: See methods B and C in Figure 3-15.
Components inside the dashed-line boxes are ports on the equipment. Components 2, 4, and 5 are
mandatory. Other components are subject to engineering procurement.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Hardware Installation Preparations
materials
(2) Hose clamp
(4) Hose delivered
with the fittings
33