7.13.2 Laying Out the Water Detection Cable (Top Pipe Routing)

Context
Figure 7-71 Laying out a water detection cable (top pipe routing)
(1) ECC800
Do not contact the water detection cable to metal, for this action will cause a false alarm. Take
protective measures when routing a water detection cable.
Procedure
Step 1 Plan the installation position for the fastener of the water detection cable. Ensure that the
water detection cable placed on the fastener is in good contact with the floor.
Step 2 Tear off the protection paper from the rear of the fastener, and then securely attach the
fastener to the floor.
Issue 04 (2017-06-30)
(2) Network cable
One fastener is provided for a 1 meter long water detection cable.
Huawei Proprietary and Confidential