Installing A Wlds900 Water Sensor (Used In Intelligent Micro-Modular); Connecting A Cable To The Wlds900 Water Detector - Huawei FusionModule2000 Installation Manual

Smart modular data center, 2000 mm high cabinets, single-row aisle containment, 380 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
7.13 Installing a WLDS900 Water Sensor (Used in
Intelligent Micro-Modular)
The water sensor mentioned in this section is configured for the smart module, rather than air
conditioners. If this water sensor is installed, you do not have to install the water sensor
configured for air conditioners.

7.13.1 Connecting a Cable to the WLDS900 Water Detector

Context
Figure 7-68 Water sensor
(1) Water detector
(4) Conversion cable end B,
connected to the water detection
cable
Issue 04 (2017-06-30)
The water sensor is composed of the water detection cable (BOM number: 33010445),
water detector (BOM number: 33010352), and conversion cable (packed with the water
detector).
The water detector is installed in the network cabinet, and bound to the rack rail at the
rear door using cable ties. The binding position is 5 U away from the cabinet bottom.
A single water detection cable is 5 meters long. If a longer cable is required, connect
multiple water detection cables to increase the length. One water detector can connect to
a maximum of nine water detection cables.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
(2) Conversion cable end A,
connected to the water detector
(5) Water detection cable end A,
connected to the conversion cable
7 Installing Monitoring Devices
(3) Conversion
cable
(6) Water
detection cable