Scenario Description - Huawei FusionModule2000 Installation Manual

Smart modular data center, 2000 mm high cabinets, single-row aisle containment, 380 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Figure 2-1 shows the floor plan of the smart module A single-row aisle containment. The PDC
is an integrated UPS. Figure 2-2 shows the exterior of the single-row aisle containment of the
smart module.
The floor plan and exterior diagrams only indicate the relative positions of components.
For the detailed installation position, see the engineering layout diagram and actual
objects.
The PDC in smart module A is an integrated UPS, with batteries deployed inside the aisle
containment.
The PDC in smart module B is an integrated PDC or precision PDC, with batteries and
UPS deployed outside the aisle containment.
The PDC in smart module A (with batteries deployed outside) is an integrated UPS, with
batteries deployed outside the aisle containment.
You are advised to deploy two air conditioners that support heating and humidification in
standard configuration. Place the air conditioners near both ends of a single-row aisle
containment. If more than two air conditioners that support heating and humidification are
required, deploy them evenly based on site requirements.
To attach labels to the cabinets, name the single-row aisle containment row A, as shown in Figure 2-1.
Issue 04 (2017-06-30)
2
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.

Scenario Description

2 Scenario Description
16

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents