Figure 3-47 Positioning the first base
Step 5 Use the end cabinet base as the reference and place other cabinet bases.
Step 6 Check that L1, L2, L3, and L4 meet the following requirements: |L1–L2| ≤ 5 mm and |L3–L4|
≤ 5 mm.
Figure 3-48 Base layout (unit: mm)
Step 7 Use a marker to mark hole positions.