Humidifier Water Inlet Pipe, Pump Drainpipe, And Automatic Drainpipe - Huawei FusionModule2000 Installation Manual

Smart modular data center, 2000 mm high cabinets, single-row aisle containment, 380 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Figure 3-2 Oil trap and inverted traps (unit: mm)
Table 3-2 Specifications for oil traps and inverted traps
No.
1
2
3
Note: After the traps are made, verify that the surface is smooth and even.
3.1.2.4 Humidifier Water Inlet Pipe, Pump Drainpipe, and Automatic
Drainpipe
Drainpipes must be able to withstand temperatures higher than 85° C. Otherwise, the pipes
may be deformed. This notice is for the equipment configured with a humidifier.
Table 3-3 and Figure 3-3 describe how to install the humidifier water inlet pipe, pump
drainpipe, and automatic drainpipe.
Issue 04 (2017-06-30)
Name
Oil trap
Gas pipe inverted
trap
Liquid pipe inverted
trap
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Hardware Installation Preparations
Copper Pipe
Outer Diameter
and Thickness
22.2 mm x 1.2 mm
22.2 mm x 1.2 mm
15.9 mm x 1.0 mm
Technical
Requirements
The flaring inner
diameter of the
copper pipe is 22.4
mm, and the necking
outer diameter is
19.5 mm.
The flaring inner
diameters at both
ends of the copper
pipe are 22.6 mm.
The flaring inner
diameters at both
ends of the copper
pipe are 16.3 mm.
21