Step 4 Adjust the gap between door panels.
After the door panels are installed and closed, the gap between panels may be uneven and
look ungraceful, as described in Table 5-2. If the gaps are even, skip this procedure.
Table 5-2 Door gap faults
Fault Type
Tilted door panel
Varying gap between the
door panel and the upper
frame mounting kit
Door mismatch
1.
Both methods must ensure that there is no gap between the post bottom and the floor.
Issue 04 (2017-06-30)
Figure 5-20 shows a tilted door. You can solve the problem in the following ways:
If the door tilts by a large degree, adjust the anchor bolts of the cabinet. If a post is
lifted off the floor due to the adjustment, add a spacer under the post.
If the door slightly tilts, add a spacer under the corresponding post to correct the tilt.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Root Cause
The left and right cabinets
onto which the upper frame
mounting kit is hung are not
on the same level, or the
upper frame mounting kit
and posts are tilted because
the floor is uneven.
One post has tilted, or the
door does not match with
the upper frame mounting
kit due to a manufacturing
error.
The left and right cabinets
onto which the upper frame
is hung are not on the same
level.
5 Installing the Contained Aisles
Solution
For details about the
adjusting method, see
4.1.
For details about the
adjusting method, see
4.2.
For details about the
adjusting method, see
4.3.
Step
Step
Step
104