FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Figure 3-8 Position of the water tank
(1) Water pan
Figure 3-9 Positions of high and low floats
(1) High float
Procedure
Step 1 Loosen the two butterfly nuts from the high and low floats in the water tank, and remove the
transport fasteners for the floats.
Step 2 Secure the butterfly nuts.