Cable Routes For The Single-Row Aisle Containment Scenario - Huawei FusionModule2000 Installation Manual

Smart modular data center, 2000 mm high cabinets, single-row aisle containment, 380 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
10.2 Cable Routes for the Single-Row Aisle Containment
Scenario
Figure 10-9 shows how power cables and signal cables are routed in the single-row aisle
containment.
Ensure that strong-current cables and weak-current cables are at least 100 mm away from
each other.