Checking The Air Pressure - Huawei FusionModule2000 Installation Manual

Smart modular data center, 2000 mm high cabinets, single-row aisle containment, 380 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Table 3-4 Cable specifications
Name
Indoor unit
power cable
Outdoor
unit power
cable
Voltage
jumper
Outdoor
unit on/off
signal cable
Water
sensor
signal cable
Teamwork
networking
cable
Temperature
and
humidity
(T/H) sensor
and its cable
a: If you use a five-core cable, do not install the neutral wire (blue). Instead, cut off it and
properly wrap PVC insulation tape around the cutting place. Purchase indoor unit power
cables with the qualified diameter (16.8–18 mm). Otherwise, the power cables will fail to
be routed through the clip.

3.1.2.7 Checking the Air Pressure

Procedure
Step 1 Open the rear door.
Step 2 Unfasten the rotating baffle plates in the air filters and remove the air filters, as shown in
Figure 3-6.
Issue 04 (2017-06-30)
Specifications
a
Four-core cable
: electrical power cable-600
V/1000 V-ZA-RVV-6 mm
L1, L2, and L3 terminals: common
terminal-single cord end terminal-6
2
mm
-0.02 m-30 A-inserted depth 12 mm
PE terminals: naked crimping terminal-OT-6
2
mm
-M6-50 A-tin plated-12 AWG to 10
AWG
For details about the cable specifications, see
the outdoor unit user manual.
Six voltage jumpers are available in the
fitting bag. Select one for use.
For details about the cable specifications, see
the outdoor unit user manual.
Power cable-5 m-22 AWG-(2 x T0.5
2
22UL1007)-(2 x T0.5
)
It can also be used for host monitoring.
N/A
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Hardware Installation Preparations
Quantity
1 PCS (The
2
-46 A
length is
determined
in presale
survey.)
6 PCS
2 PCS
1 PCS
1 PCS
1 PCS
2
)-(2 x
1 PCS
1 PCS (10
m)
Max. 6 PCS
Remarks
Optional
Mandatory
Mandatory
Optional
Mandatory
Optional
Mandatory
Mandatory
Optional
24