Figure 10-26 Directly connecting two batteries
When the length of a battery cable is longer than the distance between two battery
terminals, connect the cable in the way shown in Figure 10-27. To prevent misshaping
battery terminals, do not connect the cable in the way shown in Figure 10-28.
Figure 10-27 Correct battery cable connection method
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10 Cable Routing
198