FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Table 10-2 Relationships between the status of the indicator and the SMS modem
Indicator
On
Blinks slowly
Blinks quickly
Off
Step 5 (Optional) Install the modem driver.
----End
10.8 Connecting the Ground Cables for the Smart Module
The grounding system of the smart module must be a TN-S or TN-C-S system. The ground
resistor between the equipment ground cable and data center ground bar must be less than 0.1
ohm.
10.8.1 Grounding Cabinets
M-shaped Grounding (Recommended)
Cabinets are grounded by cables connected from the main ground bars shown by (2) in Figure
10-19 to the nearby ground grid.
Issue 04 (2017-06-30)
Normally no modem driver is required. If the modem requires a driver, install the driver according to the
modem document.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Modem
The SMS modem is activated and is not registered with
the network.
The SMS modem is connected to the network and is in
idle mode.
The SMS modem is in transmission mode.
The SMS modem is deactivated.
10 Cable Routing
192