Installing An 800 Mm Wide Cable Trough; Installing End Panels For Cable Troughs - Huawei FusionModule2000 Installation Manual

Smart modular data center, 2000 mm high cabinets, single-row aisle containment, 380 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)

6.3 Installing an 800 mm Wide Cable Trough

An 800 mm wide cable trough (BOM number: 21501140) is installed on the top of an 800
mm wide cabinet. The installation method is similar to the method for installing a 600 mm
wide cable trough. For details, see 6.1 Installing a 600 mm Wide Cable Trough.

6.4 Installing End Panels for Cable Troughs

Context
Procedure
Step 1 Hold the top of the end panel with both hands to keep it vertical. Press it from the top to the
bottom into the hooks at the end of the cable troughs until the top of the end panel is flush
with the top of the cable troughs.
Issue 04 (2017-06-30)
Typically, end panels are installed only on cable troughs of cabinets at the two ends of an
aisle.
A red panel indicates that the corresponding cable trough is for power cables, and a blue
end panel for signal cables.
Generally, the power cable trough is located close to the aisle containment, and the signal
cable trough is located far away from the aisle containment.
Obtain the cable trough end panels from the end door materials.
During the installation, the interconnecting wrench is vertical.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 (Optional) Installing Cable Troughs
121

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents