(7) Column in the
equipment room
If a column in the data center is irregular, ensure that the maximum cross section of the
column does not interfere with cabinets.
Figure A-5 Column in the aisle containment (A < 800 mm)
Issue 04 (2017-06-30)
skylight
Cabinet places on the column side are left blank and sealed by sealing plates. Directions of the
concave sides of the sealing plates are shown in Figure A-5.
Install cable trays over the cabinets on both sides of the blank cabinet place for routing
strong-current and weak-current cables.
Install an adjustable skylight over the aisle containment. The area to be covered by the adjustable
skylight is shown in Figure A-5.