FusionModule2000 Smart Modular Data Center
Product Description (380 V)
3.1.11 Scenario with Columns
The smart module supports the scenario with columns if the following conditions are met:
Figure 3-13 Legend
(1) Cabinet
(4) Flat or rotating
skylight
(7) Column in the
equipment room
Issue 04 (2017-06-30)
The dimensions of a column in the data center are not greater than 1100 mm x 1100 mm.
There are less than two columns in the same aisle width direction.
If a column is located at an end of the smart module, the smart module supports only the
revolving door.
If a column in the data center is irregular, ensure that the maximum cross section of the
column does not interfere with cabinets.
(2) Single layer of
cable tray
(5) Adjustable
skylight
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 System Architecture
(3) Double layer of cable trays
(6) Two connected sealing plates with the
concave sides facing rightwards
21