APPENDIX F
APPENDIX F IEC 60870-5-103 PROTOCOLF.1IEC 60870-5-103 PROTOCOL
The F650 implements functionality of an IEC 60870-5-103 server.
This section describes the protocol IEC 60870-5-103 implementation in the unit.
1.
PHYSICAL LAYER
Electrical interface
X
EIA RS-485
32
Number of loads for one protection equipment
Optical interface
X
Glass fibre
X
Plastic fibre
F-SMA type connector
X
BFOC/2,5 type connector
Transmission speed
X
9600 bits/s
X
19200 bits/s
2.
LINK LAYER
There are no choices for the link layer.
3.
APPLICATION LAYER
Transmission mode for application data
Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion standard.
Common address of ASDU
X
One COMMON ADDRESS OF ASDU (identical with station address)
More than one COMMON ADDRESS OF ASDU
Selection of standard information numbers in monitor direction
System functions in monitor direction
INF
Semantics
X
<0>
End of general interrogation
X
<0>
Time synchronization
X
<2>
Reset FCB
X
<3>
Reset CU
X
<4>
Start/restart
X
<5>
Power on
GEK-106310AB
F650 Digital Bay Controller
F.1 IEC 60870-5-103 PROTOCOL