GE F650 Instruction Manual page 423

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

7.2 IEC 61850 PROFILE FOR F650
2 PIXIT for Server model
Description
Which analogue value (MX) quality bits are supported
(can be set by server)
Which status value (ST) quality bits are supported (can be
set by server)
What is the maximum number of data values in one
GetDataValues request
What is the maximum number of data values in one
SetDataValues request
Additional Items:
Behaviour of stepSize attribute checks
7
3 PIXIT for Dataset model
Description
What is the maximum number of data elements in one
data set
How many persistent data sets can be created by one or
more clients
How many non-persistent data sets can be created by one
or more clients
7-54
Value / Clarification
Validity:
Y Good,
N Invalid,
N Reserved,
N Questionable
N Overflow
N OutofRange
N BadReference
N Oscillatory
N Failure
N OldData
N Inconsistent
N Inaccurate
Source:
Y Process
N Substituted
N Test
N OperatorBlocked
Validity:
Y Good,
N Invalid,
N Reserved,
N Questionable
N BadReference
N Oscillatory
N Failure
N OldData
N Inconsistent
N Inaccurate
Source:
Y Process
N Substituted
N Test
N OperatorBlocked
MMS PDU SIZE / 4
MMS PDU SIZE / 4
When a client attempts to write value of setVal (CDC ING)
or setMag (CDC ASG) which is not a multiple of stepSize
attribute of assciated CF then the device will truncate the
value to the nearest stepSize not greater than the value
intended to be written.
Value / Clarification
Data sets cannot be created via MMS services.
Data sets can be created via ICD/CID file and maximum
number of elements in one data set is 64. The exception to
that is the predefined data set "eveGGIO1$ST" which
contains 192 elements.
Data sets cannot be created via MMS services.
Data sets can be created via ICD/CID file and maximum
number of all persistent data sets in F650 relay is 20.
0