System Info; Record Status - GE F650 Instruction Manual

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

6.2 STATUS
This screen can be accessed at Actual> Status > Flex Curves, and it includes the internal flex curves status.
If the LED associated to the FlexCurve status is lit up, this indicates that the user curve has been configured with new
values (not default values).
Table 6–29: FLEX CURVES STATUS
This screen can be accessed at Actual> Status > System Info. It can monitor the system parameters and the internal
status of the Relay operative system.
This screen shows part of the information related to the different records stored in the Relay, such as:
6.2.12.1 FAULT REPORTS
Actual> Status > Records Status > Fault Reports
Table 6–30: FAULT REPORT STATUS
6
FAULT REPORT TRIGG:
CLEAR FAULT REPORTS: This signal indicates the reset of fault reports.
FAULT DATE:
FAULT TYPE:
FAULT LOCATION:
FAULT REPORT NUMBER: Number of fault reports available in the relay (ten is the maximum number of records
6-24
FLEX CURVES STATUS
FLEXCURVE A STATUS
FLEXCURVE B STATUS
FLEXCURVE C STATUS
FLEXCURVE D STATUS
FAULT REPORT STATUS
FAULT REPORT TRIGG
CLEAR FAULT REPORTS
FAULT DATE
FAULT TYPE
FAULT LOCATION
FAULT REPORT NUMBER
This signal indicates whether the signal that initiates the calculation of the distance to the fault
has been activated.
Date and time of the last fault produced in the relay. In format (Day/Month/year
Hour:minutes:seconds.milliseconds)
Type of the last fault produced in the Relay (phase to ground, phase to phase, three-phase,
etc).
Location of the last fault produced in the relay.
supported by the relay).
F650 Digital Bay Controller
6 ACTUAL VALUES
6.2.10 FLEX CURVES

6.2.11 SYSTEM INFO

6.2.12 RECORD STATUS

GEK-106310AB

Advertisement

Table of Contents
loading

Table of Contents