7 IEC 61850 PROTOCOL
2.3.2 RREC (Autoreclosing)
This logical node class is used for autorecloser and has 1 instance inside the device.
RREC class
Attribute
Attribute
Name
Type
RREC
Data
Common Logical Node Information
Mod
INC
Beh
INS
Health
INS
Status Information
Op
ACT
AutoRecSt
INS
AutoRecLo
INS
AutoRecBlk
INS
Settings
Rec1Tmms
ING
Rec2Tmms
ING
Rec3Tmms
ING
Rec4Tmms
ING
RclTmms
ING
MaxNumShot
ING
RsTmms
ASG
HoldTmms
ASG
CondEna
SPG
RRECEna
SPG
Notes:
AutoRecSt object includes extra enum values specified by Tissue 3 and Tissue 133 (See the Enum types implementation
section) .
ACT includes origin attribute in ST, this is implemented according to Tissue 68.
GEK-106310AB
Explanation
Autoreclosing
Mode
Behaviour
Health
Operate
Auto Reclosing status
Auto Reclosing Lockout Status
Auto Reclosing Block Status
First Reclose Time
Second Reclose Time
Third Reclose Time
Fourth Reclose Time
Reclaim Time
Max number of Shots
Reclosing --> Ready
Cond Check Time
Check Cond (Enable, Disable)
Function Enable, Disable
F650 Digital Bay Controller
7.2 IEC 61850 PROFILE FOR F650
M/O/E
Notes
M
Status-only
M
M
M
AR Close Breaker
M
AR Status
E
AR Lockout Mode
E
AR Block Mode
O
Dead Time 1
Units in miliseconds
O
Dead Time 2
Units in miliseconds
O
Dead Time 3
Units in miliseconds
E
Dead Time 4
Units in miliseconds
O
Reclaim Time
Units in miliseconds
E
Max number Shots
E
Reset Time
E
Hold Time
E
Cond Permission
E
Function Permission
7