GE F650 Instruction Manual page 399

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

7.2 IEC 61850 PROFILE FOR F650
2.2.4 PTOV (Overvoltage)
2.2.4.1 phsPTOV
This logical node class is used for phase overfvoltage and has 3 instances inside the device.
PTOV class
Attribute
Name
PTOV
Data
Common Logical Node Information
Mod
Beh
Health
NamPlt
Status Information
Str
Op
Blk
Settings
StrVal
OpDlTmms
RsDlTmms
PhLogic
PTOVEna
Note: ACT includes origin attribute in ST, this is implemented according to Tissue 68.
2.2.4.2 auxPTOV
This logical node class is used for auxiliary overfvoltage and has 3 instances inside the device.
PTOV class
Attribute
Name
7
PTOV
Data
Common Logical Node Information
Mod
Beh
Health
NamPlt
Status Information
Str
Op
Blk
Settings
StrVal
OpDlTmms
RsDlTmms
PTOVEna
Note: ACT includes origin attribute in ST, this is implemented according to Tissue 68.
7-30
Attribute
Explanation
Type
Overvoltage
INC
Mode
INS
Behaviour
INS
Health
LPL
Name plate
ACD
Start
ACT
Operate
ACT
Block
ASG
Start Value
ING
Operate Delay Time
ING
Reset Delay Time
ING
Logic Mode
SPG
Function TOV enable
Attribute
Explanation
Type
Overvoltage
INC
Mode
INS
Behaviour
INS
Health
LPL
Name plate
ACD
Start
ACT
Operate
ACT
Block
ASG
Start Value
ING
Operate Delay Time
ING
Reset Delay Time
SPG
Function TOV enable
F650 Digital Bay Controller
7 IEC 61850 PROTOCOL
M/O/E
Notes
M
Status-only
M
M
M
M
TOV PKP
O
TOV OP
E
TOV BLK
O
Pickup Level (3 – 300)
O
Trip Delay ( 0 – 900000 )
Units in miliseconds
O
Reset Delay ( 0 – 900000 )
Units in miliseconds
E
Logic ( Any, two, all phases )
E
Function
M/O/E
Notes
M
Status-only
M
M
M
M
TOV PKP
O
TOV OP
E
TOV BLK
O
Pickup Level (3 – 300)
O
Trip Delay ( 0 – 900000 )
Units in miliseconds
O
Reset Delay ( 0 – 900000 )
Units in miliseconds
E
Function