Advertisement

5 SETTINGS
CntPulses Factor:
CntPulses Overflow:
CntPulses Board Origin:
CntPulses Input Origin:
The signals related to the 8 pulse counters can be viewed at Actual> Status > Control Elements > Pulse Counters and
they are as follows:
Table 5–91: PULSE COUNTERS STATUS
The F650 includes eight different pulse counters in which the value shown is the result of the number of activation of the
input configured for that counter multiplied plus the CntPulses Factor set for that pulse. For each pulse counter there are
two magnitudes available, the actual value and the frozen value.
The freeze and unfreeze and reset operations are similar to the energy management, the signals used for that purpose are
the same for both energy and pulse counters.
By default, all the values are unfreeze, updating the values in a continuous mode. After a freeze operation the freeze value
stops updating and the actual value is being updated. If a freeze operation is set again, the actual value will be copied to
the freeze one, which will remain frozen again.
To unfreeze all the values it is necessary to perform an unfreeze operation.
If a reset operation is set, all the values, actual and frozen ones will go to zero.
All the operations (freeze, unfreeze and reset) are performed over all the energy counters (both energy and pulse
counters). It is not possible to set them to a particular counter.
GEK-106310AB
This is the factor multiplier applied to the input activations number stored in the
pulse counter, providing possibilities to adjust the obtained value to any scale. It the
"CntPulses Factor X" is set to zero it will take no effect.
It is the maximum value set as result of the CntPulses Factor plus the number of
inputs activation. This means that after reaching that value, the pulse counter value
will start counting from zero.
Board selection for the pulse counter input.
Index of the input select in the board origin.
PULSE COUNTERS STATUS
CntPulses Value 1
CntPulses Value 2
CntPulses Value 3
CntPulses Value 4
CntPulses Value 5
CntPulses Value 6
CntPulses Value 7
CntPulses Value 8
CntPulses Freeze 1
CntPulses Freeze 2
CntPulses Freeze 3
CntPulses Freeze 4
CntPulses Freeze 5
CntPulses Freeze 6
CntPulses Freeze 7
CntPulses Freeze 8
F650 Digital Bay Controller
5.5 CONTROL ELEMENTS
5-111
5