6 ACTUAL VALUES
6.3.1.2 VOLTAGE
Actual> Metering > Primary Values > Voltage
Table 6–38: VOLTAGE PRIMARY VALUES
6.3.1.3 POWER
Actual> Metering > Primary Values > Power
Table 6–39: POWER PRIMARY VALUES
NOTE: If voltage inputs are configured in Delta connection and the auxiliary voltage input is set as Vx, measurements of
single phase power value cannot be duly calculated, and therefore, its value will be zero. For the three-phase power value,
the system uses the ARON method, or two-wattmeters method.
GEK-106310AB
DESCRIPTION
UNITS
PT Ratio
N/A
Va Angle
Deg
Vb Angle
Deg
Vc Angle
Deg
Vn Angle
Deg
Vx Angle
Deg
Vab Angle
Deg
Vbc Angle
Deg
Vca Angle
Deg
V0 Primary
KV
V1 Primary
KV
V2 Primary
KV
Vab Primary
KV
Vbc Primary
KV
Vca Primary
KV
Va Primary
KV
Vb Primary
KV
Vc Primary
KV
Vn Primary
KV
Vx Primary
KV
VBB Primary
KV
VL Primary
KV
DESCRIPTION
Phase A Real Pwr
Phase A Reactive Pwr
Phase A Apparent Pwr
Phase B Real Pwr
Phase B Reactive Pwr
Phase B Apparent Pwr
Phase C Real Pwr
Phase C Reactive Pwr
Phase C Apparent Pwr
3 Phase Real Pwr
3 Phase Reactive Pwr
3 Phase Apparent Pwr
Phase A Power Factor
Phase B Power Factor
Phase C Power Factor
3 Phase Power Factor
F650 Digital Bay Controller
UNITS
MW
MVAr
MVA
MW
MVAr
MVA
MW
MVAr
MVA
MW
MVAr
MVA
N/A
N/A
N/A
N/A
6.3 METERING
6
6-29