5 SETTINGS
AR BLOCK BY PULSE
Autoreclose blocked by pulse. See AR block signals configuration (AR PULSE BLOCK)
AR STATUS
Autoreclose status (see Table 5–82:)
AR LOCKOUT MODE
Autoreclose lockout mode (see Table 5–82:)
AR BLOCK MODE
Autoreclose block mode (see Table 5–82:)
5.5.5.5 GENERAL AUTORECLOSE STATUS DIAGRAM
The following diagram describes the different autoreclose states, as well as the transitions between states.
Description of the general autoreclose status:
OUT OF SERVICE / AR DISABLE
In this status, the autoreclose is disabled. From any state, if the Function setting is set as DISABLED, the autoreclose will
move to OUT OF SERVICE status, where it is not operative.
AR READY
This is the initiation and normality situation status: closed breaker. There are neither faults producing a autoreclose
initiation nor Block signal.
If the autoreclose was in LOCKOUT, if the breaker is closed and the time set in Reclaim Time setting expires, the
autoreclose will go to the initial status of READY.
From RECLOSE IN PROGRESS, the recloser will move to READY, if the Reset Time setting expires without any
autoreclose initiation condition.
AR RECLOSE IN PROGRESS
GEK-106310AB
Figure 5–26: GENERAL AUTORECLOSE STATUS DIAGRAM
F650 Digital Bay Controller
5.5 CONTROL ELEMENTS
5-101