2.4 TECHNICAL SPECIFICATIONS
2.4.2.6 LOCKED ROTOR (48)
Current Input
Rated current
Full Load Current
Pickup level
2
Dropout level
Level accuracy for primary magnitudes
Trip delay
Reset delay
Operate time
Timing accuracy
Snapshot Events
2.4.2.7 PULSE COUNTERS
Number of Pulse counters available
Multiplier factor
Overload factor
Board Origin
Input origin
2.4.2.8 ANALOG COMPARATORS
Analog Input
Analog Maximum Threshold value
Analog Minimum Threshold value
Analog Delay
Analog Hysteresis
Analog Direction (for activation inside or outside the
deadband)
2-18
Phasor (without harmonics) or RMS
For connection to 1 or 5 A CTs.
0.10 to 10.00 kA in steps of 0.01 kA
1.01 to 109.00 in steps of 0.01 x FLC
97% to 98% of the pickup level
±3% complete range.
0.00 to 900.00 s. in steps of 0.01 s.
0.00 to 900.00 s. in steps of 0.01 s.
20 ms at 3 x Pickup at 50 Hz, typically
±3% of operate time or 50 ms. (whichever is greater)
Selectable by setting
Up to 8
0.000 to 65000.000 in steps of 0.001
0 to 1000000 in steps of 1
All available input/outputs boards in the device. See
ordering code [F, G, H, J]
up to 32 [depending on the board type selection]
Any analog value available in the device
-100000.000 to 100000.000 in steps of 0.001
-100000.000 to 100000.000 in steps of 0.001
0.00 to 900.00 in steps of 0.01
0.0 to 50.00 in steps of 0.1
IN or OUT