B.7 MEMORY MAP
ADDRESS BIT
NAME
Ajustes Sobreintensidad Temporizada de Tierra Sensible Grupo 1 - Sensitive Ground TOC 1 Settings(cont.)
B
0x24A6
TD Multiplier
0x24A8
Reset
0x24A9
Snapshot Events
0x24BC
Confirmation address
Ajustes Sobreintensidad Temporizada de Tierra Sensible Grupo 2 - Sensitive Ground TOC 2 Settings
0x24BD
Function
0x24BE
Input
0x24BF
Pickup Level
0x24C1
Curve
0x24C2
TD Multiplier
0x24C4
Reset
0x24C5
Snapshot Events
0x24D8
Confirmation address
B-78
FORMAT STEP MODE LENGTH MISCELLANEOUS
F003
1
R/W
2
F012
1
R/W
1
F012
1
R/W
1
W
1
F012
1
R/W
1
F012
1
R/W
1
F003
1
R/W
2
F012
1
R/W
1
F003
1
R/W
2
F012
1
R/W
1
F012
1
R/W
1
W
1
F650 Digital Bay Controller
APPENDIX B
12=ANSI Very Inv
13=ANSI Norm Inv
14=ANSI Mod Inv
15=I2t
16=Definite Time
17=Rectifier Curve
18=User Curve A
19=User Curve B
20=User Curve C
21=User Curve D
[0.00 , 900.00] s
0=INSTANTANEOUS
1=LINEAR
0=DISABLED
1=ENABLED
0=DISABLED
1=ENABLED
0=PHASOR(DFT)
1=RMS
[0.005 , 16.000] A
0=IEEE Ext Inv
1=IEEE Very Inv
2=IEEE Mod Inv
3=IEC Curve A
4=IEC Curve B
5=IEC Curve C
6=IEC Long-Time Inv
7=IEC Short-Time Inv
8=IAC Ext Inv
9=IAC Very Inv
10=IAC Mod Inv
11=ANSI Ext Inv
12=ANSI Very Inv
13=ANSI Norm Inv
14=ANSI Mod Inv
15=I2t
16=Definite Time
17=Rectifier Curve
18=User Curve A
19=User Curve B
20=User Curve C
21=User Curve D
[0.00 , 900.00] s
0=INSTANTANEOUS
1=LINEAR
0=DISABLED
1=ENABLED