7 IEC 61850 PROTOCOL
The following list explains the available options for each tab:
ICD/CID
•Receive ICD file from the relay
•Send configured ICD (CID file) to the relay
•Configure IED Name and Logical Device Instance
•Configure IP address, netmask and gateway
•Configure deadbands (db) of measurement values
•Configure control models (ctlModel) of controllable objects
Reports
•Create Data Sets for IEC 61850 Reports
•Select between Buffered Reports or Unbuffered Reports
•Configure Reports Control Block parameters
GOOSE Reception
•Configure reception part for GOOSE messages
GOOSE Transmission
•Configure transmission part for GOOSE messages
a) ICD/CID CONFIGURATION TAB
The ICD Explorer window allows the user to navigate through the ICD file. The data is organized in a hierarchical mode.
The user can browse through the data model of the relay and change desired IEC 61850 parameters like Logical Device
Name, prefixes of Logical Nodes, IP address, etc.
When a parameter is selected in the ICD Explorer window then the Attributes window appears on the right part of the
screen:
GEK-106310AB
Figure 7–9: ATTRIBUTES WINDOW
F650 Digital Bay Controller
7.3 IEC 61850 CONFIGURATOR
7
7-63