7.2 IEC 61850 PROFILE FOR F650
A and T profiles can be combined in various ways to form different types of services and information items that can be
exchanged. The services specified in Part 7-2 of the IEC61850 standard are mapped onto four different combinations of the
profiles. These four combinations are used for
•
Client/server services,
•
GOOSE/GSE management services,
•
GSSE services,
•
Time synchronization,
•
Services for measured value sampling.
7.2.7.3 CONFORMANCE STATEMENTS FOR F650 DEVICES
Product's protocol and model implementation conformance statements:
•
"PICS for 650 family of relays v1_7 firm3_60"
•
"MICS for 650 family rev1.4 firm3_60"
•
"TICS for 650 family of relays v1_7 firm3_60"
•
"PIXIT for 650 family of relays v1_5 firm3_60"
7.2.7.3.1 PICS FOR 650 FAMILY OF RELAYS
Reference documentation: PICS for 650 family rev1_7 firm3_60. This document describes the:
•
ACSI Conformance Statement
•
PICS ("Protocol Implementation Conformance Statement") for 650 family of relays.
1 ACSI Conformance Statement
The following ACSI conformance statements shall be used to provide an overview and details about a device claiming con-
formance with ACSI to specify the communication features mapped to an SCSM:
•
ACSI BASIC conformance statement.
7
•
ACSI MODELS conformance statement.
•
ACSI SERVICE conformance statement.
1.1 Notation
For the following clauses, these definitions apply:
•
Y: The item is implemented.
•
N: The item is not implemented.
•
AA: Application Association.
•
TP: Two-party (application association).
•
MC: Multicast (application association).
7-10
F650 Digital Bay Controller
7 IEC 61850 PROTOCOL
GEK-106310AB