3 HARDWARE
3.4 WIRING

3.4.3 CABLE/FIBER ETHERNET BOARD

The Ethernet board is the communication board 2 (COM3) shown in Figure 3–2:. It is located in the bottom at the rear part
of the relay.
In Models C and D, the 10/100BaseTX port is selected by an internal switch. To select between fiber and cable it is
necessary to extract the board, switch the jumper to the selected position, as indicated on Figure 3–10: FIBER/CABLE
SELECTION and insert the board again. As with any other relay manipulation, the relay power supply must be removed
and the operation must be performed only by skilled personnel.
The default port selected by switch is 10/100 TX in factory configuration. The switch selects between cable (10/100 TX) and
the first fiber port (100 FX). In Ethernet board type D (double fiber port) the backup channel is always fiber.
3
Figure 3–10: FIBER/CABLE SELECTION
GEK-106310AB
F650 Digital Bay Controller
3-11