GE F650 Instruction Manual page 221

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

5.4 PROTECTION ELEMENTS
Table 5–66: 59NH/59NL ELEMENT SETTINGS
SETPOINT > PROTECTION ELEMENTS > VOLTAGE ELEMENTS >
>NEUTRAL OV HIGH > NEUTRAL OV HIGH 1> NEUTRAL OV HIGH 2 > NEUTRAL OV HIGH 3
>NEUTRAL OV LOW > NEUTRAL OV LOW 1> NEUTRAL OV LOW 2 > NEUTRAL OV LOW 3
SETTING DESCRIPTION
Function permission
Pickup Level
Trip time
Reset time
Snapshot Event generation
The snapshot event setting enables or disables the snapshot event generation for this element.
5.4.8.4 NEGATIVE SEQUENCE OVERVOLTAGE ELEMENT (47)
The Negative sequence phase overvoltage element uses as its input magnitude the negative sequence component
calculated from the phase voltage values. This element can be used to detect the loss of one or two phases, unbalance
voltage conditions, etc.
Table 5–67: 47 ELEMENT SETTINGS
SETPOINT > PROTECTION ELEMENTS > VOLTAGE ELEMENTS > NEGATIVE SEQUENCE OV >
NEGATIVE SEQUENCE OV 1> NEGATIVE SEQUENCE OV 2 > NEGATIVE SEQUENCE OV 3
SETTING DESCRIPTION
5
Function permission
Pickup Level
Trip time
Reset time
Snapshot Event generation
The snapshot event setting enables or disables the snapshot event generation for this element.
5.4.8.5 AUXILIARY OVERVOLTAGE ELEMENT (59X)
This is an Auxiliary overvoltage element for general use that uses as its input magnitude the voltage measured by the 4
VT (when VX is selected as Auxiliary Voltage in General Settings). The time delay for element 59X can be set from 0 to 900
seconds. The element has a reset than can be programmed from 0 to 900 seconds.
Table 5–68: 59X ELEMENT SETTINGS
SETPOINT > PROTECTION ELEMENTS > VOLTAGE ELEMENTS > AUXILIARY OV >
AUXILIARY OV 1> AUXILIARY OV 2 > AUXILIARY OV 3
SETTING DESCRIPTION
Function permission
Pickup Level
Trip time
Reset time
Snapshot Event generation
The snapshot event setting enables or disables the snapshot event generation for this element.
5-74
NAME
DEFAULT VALUE STEP
Function
DISABLED
Pickup Level
10
Trip Delay
10.00
Reset Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT
VALUE
Function
DISABLED
Pickup Level
10
Trip Delay
10.00
Reset Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
10
Trip Delay
10.00
Reset Delay
0.00
Snapshot Events
ENABLED
F650 Digital Bay Controller
RANGE
N/A
[DISABLED – ENABLED]
1 V
[3 : 300 ]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 V
[3 : 300]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 V
[3 : 300]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
5 SETTINGS
th
GEK-106310AB

Advertisement

Table of Contents
loading

Table of Contents