7 IEC 61850 PROTOCOL
Note: actVal in BCR is imlemented as INT32.
In the F650 there are up to 16 configurable switchgears. Currently four XSWI and four CSWI are implemented and mapped
to first nine switchgears in F650. XSWI and CSWI Logical Nodes can be seen as paired objects in F650 as one pair of
XSWI and CSWI map to the same swithcgear. XSWI1 and CSWI1 map to Switchgear1, XSWI2 and CSWI2 map to
Switchgear2, etc. The difference between XSWI and CSWI in F650 is that control commands cannot be sent directly via
XSWI LN. Control commands have to be sent via CSWI LN.
In F650 relay the Circuit Breaker (XCBR1 Logical Node) by default is mapped to first switchgear (exactly like XSWI1 and
CSWI1 LNs). However it is possible to map the Circuit Breaker to any of the 16 switchgears of F650 relay. It can be done by
modification of the following setting: Setpoint->System Setup-> Breaker Settings->Number of Switchgear.
In XCBR LN for "Pos" controllable attribute all possible control models are applicable:
"direct-control-with-normal-security"
"SBO-control-with-normal-security"
"direct-control-with-enhanced-security"
"SBO-control-with-enhanced-security"
The sboTimeout attribute for Pos is configurable in a range from 500 ms to 60 seconds.
The sboClass attribute for Pos can only have value "0" (operate-once).
2.7.2 XSWI (Circuit switch)
XSWI class
Attribute
Attribute
Name
Type
XSWI
Data
Common Logical Node Information
Mod
INC
Beh
INS
Health
INS
NamPlt
LPL
Loc
SPS
EEHealth
INS
OpCnt
INS
Controls
Pos
geDPC
BlkOpn
SPC
BlkCls
SPC
Status information
SwTyp
INS
SwOpCap
INS
In the F650 there are up to 16 configurable switchgears. Currently four XSWI and four CSWI are implemented and mapped
to first nine switchgears in F650. XSWI and CSWI Logical Nodes can be seen as paired objects in F650 as one pair of
XSWI and CSWI map to the same swithcgear. XSWI1 and CSWI1 map to Switchgear1, XSWI2 and CSWI2 map to
Switchgear2, etc. The difference between XSWI and CSWI in F650 is that control commands cannot be sent directly via
XSWI LN. Control commands have to be sent via CSWI LN.
"Pos" attribute is not controllable in XSWI it has ctlModel = Status-only. In order to control the switch mapped to given XSWI
the corresponding CSWI LN should be used.
GEK-106310AB
Explanation
Circuit switch
Mode
Behaviour
Health
Name plate
Local operation
External equipment health
Operation counter
Switch position
Block opening
Block closing
Switch Type
Switch operating capability
F650 Digital Bay Controller
7.2 IEC 61850 PROFILE FOR F650
M/O/E
Notes
M
Status-only
M
M
M
M
Local / Remote
O
M
Breaker openings
M
Status-only
M
Status-only
M
Status-only
M
Fixed value = 2 (Disconnector)
M
Fixed value = 5