GE F650 Instruction Manual page 780

Digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

APPENDIX H
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>AUXILIARY OV
AUXILIARY OV 1> AUXILIARY OV 2 > AUXILIARY OV 3
SETTING DESCRIPTION
Function permission
Pickup Level
Trip Time
Reset Time
Snapshot Event generation
SETPOINT > PROTECTION ELEMENTS >VOLTAGE ELEMENTS>AUXILIARY UV
AUXILIARY UV 1> AUXILIARY UV 2 > AUXILIARY UV 3
SETTING DESCRIPTION
Function permission
Pickup Level
Curve shape
Time Dial
Snapshot Event generation
SETPOINT > PROTECTION ELEMENTS > POWER > FORWARD POWER
FORWARD POWER 1> FORWARD POWER 2 > FORWARD POWER 3
SETTING DESCRIPTION
Function permission
Block from off-line
Pickup level for stage 1
Trip time for stage 1
Pickup level for stage 2
Trip time for stage 2
Snapshot Event generation
GEK-106310AB
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
10
Trip Delay
10.00
Reset Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
10
Curve
DEFINITE TIME
Delay
10.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Blk Time After Close
0.00
Stage 1 Tap
10.00
Stage 1 Time
60.00
Stage 2 Tap
20.00
Stage 2 Time
60.00
Snapshot Events
ENABLED
F650 Digital Bay Controller
H.1 FACTORY DEFAULT SETTINGS
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 V
[3 : 300]
0.01 s
[0.00 : 900.00]]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 V
[3 : 300]
[DEFINITE TIME –
N/A
INVERSE TIME]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 s
[0.00 : 900.00]
0.01MW
[0.00 : 10000.00]
0.01 s
[0.00 : 900.00]
0.01MW
[0.00 : 10000.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
USER
VALUE
USER
VALUE
USER
VALUE
H
H-13

Advertisement

Table of Contents
loading

Table of Contents