5.10 LOGIC CONFIGURATION (PLC EDITOR)
5.10.2.2 LOGIC COMPILATION
The F650 configuration will be made using the basic operations related before and more complex operations can be
developed inside libraries.
All the graphical configuration performed in the Logic configuration editor must be read and interpreted by the PLC as the
F650 engine. The graphical equations must be translated into compiled equations to be understood by the relay. For this
purpose the logic configuration editor provides a compilation option to compile the whole configuration, creating a series of
equations that will form the logical configuration of the element.
The next diagram shows the way compiled logic equations are built.
5
A single equation is composed of one or more inputs, one or more operations, and one output. The order of equations is
determined by the relative position of their outputs.
In the following example is shown the order of compilation for equations determined by their relative position in the
configuration file:
In this case, equation A is the first to be executed. However, in the second case, the first equation to be executed would be
B, as its output is before the Equation A output.
5-158
DAT
COMPILATION
EQUATIONS
PLC
Figure 5–55: COMPILED LOGIC EQUATIONS
EQUATION A
EQUATION B
EQUATION A
EQUATION B
Figure 5–56: ORDER OF EQUATIONS
F650 Digital Bay Controller
OPERATION
PLC
EQUATION A OUTPUT
EQUATION B OUTPUT
EQUATION B OUTPUT
EQUATION A OUTPUT
5 SETTINGS
GEK-106310AB